WRAS EPDM Assembly with Stainless Steel Overbraid
Compression End Connections

Hydraflex's smooth bore EPDM lined assemblies with a 304 Stainless Steel over braid have been independently tested and permitted for potable water by The Water Regulations Approval Scheme (WRAS). Available from DN08 to DN25 and a temperature range of -20°C to +85°C, these assemblies are differentiated by a red fleck through the over br......Read More
Total : £0.00


Part NumberIDOverall LengthFitting 1Fitting 2Price each (exc. VAT)Quantity
SW13MBMB4513mm450mm15mm Compression15mm Compression£12.22
SW13MBMB6013mm600mm15mm Compression15mm Compression£13.66
SW19MBMB3019mm300mm22mm Compression22mm Compression£21.42
SW19MBMB4519mm450mm22mm Compression22mm Compression£24.87
SW19MBMB6019mm600mm22mm Compression22mm Compression£28.31
SW25MBMB3025mm300mm28mm Compression28mm Compression£39.15
SW25MBMB4525mm450mm28mm Compression28mm Compression£43.57
SW25MBMB6025mm600mm28mm Compression28mm Compression£47.98
SW13MBMB3013mm300mm15mm Compression15mm Compression£10.77
Total : £0.00


Hydraflex's smooth bore EPDM lined assemblies with a 304 Stainless Steel over braid have been independently tested and permitted for potable water by The Water Regulations Approval Scheme (WRAS). Available from DN08 to DN25 and a temperature range of -20°C to +85°C, these assemblies are differentiated by a red fleck through the over braid from our standard building services assemblies.

  • Potable Water
  • Drinking Water
Hose Part Number ID OD Working Pressure Min Bend Minimum Assembly Cut Length Coil Size Ferrule
MM MM Bar MM MM M
SW08 8 12 20 27 80 200 B13X14SS
SW10 10 14 20 40 150 150 B15X19.5SS
SW13 13 17 20 60 150 100 B18.5X19.5SS
SW19 19 27 16 80 180 50 B29X30SS
SW25 25 34 10 100 180 50 B36X38SS
 
Diagram 2 displaying the overall length and cut length of a hose assembly
The arrow on drawing D2 denotes the 'R' measurement showing the 'Minimum Bore Through Fittings (mm)' which is reduced through the fitting tail, with a tolerance of +/- 0.2mm. The below measurements represent the minimum bore of each DN size; however, fittings will vary in bore size. For further information regarding this please contact out technical department.
DN Size Hose Bore (Inches) Hose Bore (mm) R = Minimum Bore Through Fittings (mm)
DN06 1/4" 6 4.2
DN08 5/16" 8 5.7
DN10 3/8" 10 6.7
DN13 1/2" 13 8.7
DN19 3/4" 19 14.8
DN25 1" 25 19.8
DN32 1 1/4" 32 25.5
DN40 1 1/2" 40 31.8
DN50 2" 50 40.4
 
DN D R A B L Z/d90deg Z/180deg Z/d360deg
DN08 12 27 27 18 78 132 174 258
DN10 14 40 40 20 107 183 246 258
DN13 18 60 60 22 151 258 352 540
DN16 22 70 70 25 176 300 410 630
DN19 27 80 80 29 202 344 470 722
DN25 34 100 100 33 250 423 580 894
DN32 44 160 160 37 379 645 896 1398
DN40 54 180 180 50 437 743 1026 1592
DN50 64 230 230 56 548 933 1294 2016
 
Working Pressure Bar (Tolerance +/- 1 Bar)
Temperature
Part No. Bore 20°C 30°C 40°C 50°C 60°C 70°C 80°C 90°C 100°C
SW08 DN08 20 20 20 20 18 18 17 17 16
SW10 DN10 20 20 20 20 18 18 17 17 16
SW13 DN13 20 20 20 20 15 15 14 14 13
SW19 DN20 16 16 16 16 12 12 11 11 11
SW25 DN25 10 10 10 9 9 9 9 9 9
Theoretical Minimum Burst Pressure (Bar)
Temperature
Part No. Bore 20°C 30°C 40°C 50°C 60°C 70°C 80°C 90°C 100°C
SW08 DN08 120 120 120 120 115 110 100 90 66
SW10 DN10 120 120 120 120 115 110 100 90 66
SW13 DN13 90 90 90 90 88 86 83 80 53
SW19 DN20 80 80 80 80 79 78 76 75 43
SW25 DN25 60 60 60 60 58 57 56 55 36

Formula: Pc = (TxL) + R (in mbar)

Pc = Pressure Drop in mbar T = Pressure drop in mbar for one meter of hoses according to its flow capacity in M3/h (Schedule 1) L = Hose Length in meters R = Pressure drop in mbar caused by two fittings (male x female), same condition than 'T' (Schedule 2)

Flexible hose with one straight and one elbow fittings= R x 1.5 Flexible hose with two elbow fittings = R x 3 Example: Flexible hose DN13 length 500mm 1 FP - MC, flow capacity 1000 l/h Pc = (26 mbar/m x 0.5m) + 23 mbar = 36 mbar Flexible hose DN25 length 800 1 FP - FPN, flow capacity 1500 l/h Pc = (3mbar/m x 0.8m) + (2.5 mbar x 1.5) = 9 mbar Note: 'T' value only valid for hoses installed straight. Installation with bend can cause pressure drop relative to decrease in bend radius.